Power Quality Analysis for Voltage Sags, Harmonics, and Nuisance Trips

Feb 10, 2026 | Acceptance Testing

Power Quality Problems Are Event Problems

A voltage sag may last less than a second and still stop a drive, reset a controller, or interrupt a process. Harmonics can add heating without creating an obvious alarm. Voltage unbalance can affect motors while average voltage appears acceptable.

Power quality analysis captures electrical behavior over time so symptoms can be matched to events. IEEE 1159 provides consistent descriptions of power-system phenomena, monitoring techniques, applications, and interpretation.

Start With the Symptom and the Clock

The best investigation begins with exact timestamps, affected loads, alarms, operator notes, and recent electrical or production changes. A monitor placed without that context may collect large amounts of data while missing the event that matters.

Meter location is equally important. Monitoring at the service, feeder, and affected load can help separate an upstream utility event from an internal load interaction. The test duration should cover the operating cycle that produces the symptom.

What the Data Can Reveal

Useful measurements may include rms voltage and current, sags, swells, interruptions, transients, frequency, power factor, demand, voltage and current unbalance, total harmonic distortion, individual harmonics, and captured waveforms.

No single metric explains every problem. Harmonic current may be normal for a nonlinear load but still contribute to transformer or neutral heating. A sag profile may indicate a motor start, fault, or upstream event only when the waveform and facility timeline are reviewed together.

  • Synchronize monitor time with facility event logs.
  • Record one-line location and current-transformer orientation.
  • Capture representative production cycles.
  • Turn conclusions into specific corrective or monitoring actions.

Separate the Source From the Susceptibility

A disturbance and a process interruption are related but not identical. The same voltage sag may stop one drive while another rides through it. Investigation should consider both the electrical event and the affected equipment’s settings, controls, protection, and tolerance.

That distinction prevents an incomplete conclusion such as ‘the utility caused it’ or ‘the drive is bad.’ The best corrective path may involve the source, the facility distribution system, or the load’s ride-through and control design. Event waveforms and equipment logs provide the evidence to decide where action belongs.

From Analysis to a Practical Fix

Corrective action may involve settings, conductor or transformer capacity, load balancing, grounding, filtering, ride-through, sequencing, or a permanent monitoring strategy. Currentechnologies’ partnership with Schneider Electric supports the connected-system capabilities described on its EcoXpert partnership page.

Power quality analysis is listed among Currentechnologies’ core qualifications. To discuss a recurring trip, sensitive-load issue, or monitoring plan, contact Currentechnologies.